To avoid these ads, REGISTER NOW!

Connecting to Power - Single Phase 230v 5 hp Air Compressor - Ingersoll Rand

bulletpruf

Well-known member
Joined
Nov 28, 2013
Messages
10,864
Location
San Antonio
Electrical stuff generally makes my head hurt, but I just got a new IR air compressor from Tractor Supply - https://www.tractorsupply.com/tsc/p...OPygWrEEKNKHvKCxlkIflG8CoJsP9jMxoCecoQAvD_BwE - it's single phase, two stage, 5 hp.

The specs state: 21.5 Full Load Amps, Recommended Breaker Amp Size 40, Recommended Wire Gauge <50 ft. 8 Gauge (8 AWG).

I have 230v connected to a 30 amp (i.e., smaller than recommended) breaker traveling about 30' to a box on the wall next to the compressor.

I do have the instructions, but they're generic for several different models of compressor.

I'm inclined to hard-wire the compressor, but I would be ok with a plug, too.

I guess my first step is to confirm that I have 8 gauge wire going from the panel to the box on the wall.

Scott

IMG_6241.JPG

I don't have a recent picture of the panel since the compressor breaker was added, but I'll get one.

1779373959867.jpeg

1779374171097.jpeg
 
Last edited:
To avoid these ads, REGISTER NOW!

mm08822

Well-known member
Joined
Jan 13, 2012
Messages
5,763
Location
NJ
To be certain, you should post a pic of the motor nameplate (not the compressor nameplate.)

If the motor nameplate states 5 Hp @21.5A, I would use the #10s you already have in place. The disconnect needs to be verified that it is rated for at least 5HP at 240vac. Replace if not. ( A new installation would base numbers off of 28A and not your 21.5A for current code requirements.)

The 2pole 30a cb may be able to handle the start-up current. If not, replace it with a 2 pole 40a cb.

Hardwire straight to the disconnect otherwise a plug and receptacle needs to be rated for 5 hp also. (Those are expensive and are rarely needed.)

ETA: I'm assuming you have 10's in place already.
 
Last edited:
OP
B

bulletpruf

Well-known member
Joined
Nov 28, 2013
Messages
10,864
Location
San Antonio
To be certain, you should post a pic of the motor nameplate (not the compressor nameplate.)

If the motor nameplate states 5 Hp @21.5A, I would use the #10s you already have in place. The disconnect needs to be verified that it is rated for at least 5HP at 240vac. Replace if not. ( A new installation would base numbers off of 28A and not your 21.5A for current code requirements.)

The 2pole 30a cb may be able to handle the start-up current. If not, replace it with a 2 pole 40a cb.

Hardwire straight to the disconnect otherwise a plug and receptacle needs to be rated for 5 hp also. (Those are expensive and are rarely needed.)

I'll get a picture of the motor nameplate when I confirm wire size.

Gotcha on the disconnect.
 

wyliesdiesels

Well-known member
Joined
Aug 14, 2012
Messages
19,965
Location
Modesto, CA
motor circuits are easy

wire sized 125% of NEC FLC table amps (28a for 5HP as listed on nameplate not compressor label). This means 35a rated wire for 5hp

disconnect needed if more than 50' from and not within sight of panel

must be hardwired unless you can find plug and receptacle rated for 5 or more HP
 

Firebrick43

Well-known member
Joined
May 12, 2015
Messages
13,897
Location
West central Indiana
motor circuits are easy

wire sized 125% of NEC FLC table amps (28a for 5HP as listed on nameplate not compressor label). This means 35a rated wire for 5hp

disconnect needed if more than 50' from and not within sight of panel

must be hardwired unless you can find plug and receptacle rated for 5 or more HP
To add to this, there are no inexpensive plugs and receptacles that are rated over 3 hp. All the NEMA ones are limited to 3 hp. Pin and socket plugs/receptacles get really salty if its actually listed.
 

micromind

Well-known member
Joined
Sep 24, 2023
Messages
2,976
Location
Fernley, Nevada, about 30 miles east of Reno.
motor circuits are easy

wire sized 125% of NEC FLC table amps (28a for 5HP as listed on nameplate not compressor label). This means 35a rated wire for 5hp

disconnect needed if more than 50' from and not within sight of panel

must be hardwired unless you can find plug and receptacle rated for 5 or more HP

This is true however, it should be noted that the #14/15A #12/20A #10/30A rules do not apply to motors. Use the 75C column in the NEC.

#14=20 amps, #12 = 25 amps and #10 = 35 amps.
 
OP
B

bulletpruf

Well-known member
Joined
Nov 28, 2013
Messages
10,864
Location
San Antonio
motor circuits are easy

wire sized 125% of NEC FLC table amps (28a for 5HP as listed on nameplate not compressor label). This means 35a rated wire for 5hp

disconnect needed if more than 50' from and not within sight of panel

must be hardwired unless you can find plug and receptacle rated for 5 or more HP

Panel is about 30' from the compressor and within eyesight, so I'm ok if I don't need the disconnect.

thanks
 
OP
B

bulletpruf

Well-known member
Joined
Nov 28, 2013
Messages
10,864
Location
San Antonio
Went to the shop. Here's the label on the motor. Looks like 19 amps but with a max of 22.5 amps, right? 30A breaker and #10 AWG sufficient for this?

IMG_6269.JPG

Here's a current shot of the panel.

1779404955864.jpeg

There's 10 gauge solid core wire at the junction box next to the compressor.

1779405076048.jpeg

At the panel, there's 10 gauge braided core wire coming off the 30 amp breaker for the air compressor circuit. The braided core and solid core wires are spliced together at a junction box about halfway down the run.

1779405185876.jpeg

And here's the junction box that's halfway down the run. This is where I was doing to potentially get power for my Bridgeport clone mill (single phase 230v or potentially 3 phase). This is where the braided 10 gauge wire is connected to the solid core 10 gauge wire with wire nuts.

1779405296062.jpeg

Any thoughts on how I should do this? If I have to run 8 gauge wire, I can live with that, but if 10 gauge is sufficient, I'm ok with sticking with that, of course.

I did a quick search and it appears that connecting solid to braided wires isn't unsafe.
 
To avoid these ads, REGISTER NOW!

Firebrick43

Well-known member
Joined
May 12, 2015
Messages
13,897
Location
West central Indiana

wyliesdiesels

Well-known member
Joined
Aug 14, 2012
Messages
19,965
Location
Modesto, CA
This is true however, it should be noted that the #14/15A #12/20A #10/30A rules do not apply to motors. Use the 75C column in the NEC.

#14=20 amps, #12 = 25 amps and #10 = 35 amps.

correct, have to read past 240.4(D) however the ampacity of NM-b doesnt change regardless if its feeding a motor. for 5HP, 35a rated wire is required. this means #10 THWN or #8 NM-b because #10 NM-b is limited to 30a
 
Last edited:

wyliesdiesels

Well-known member
Joined
Aug 14, 2012
Messages
19,965
Location
Modesto, CA
Went to the shop. Here's the label on the motor. Looks like 19 amps but with a max of 22.5 amps, right? 30A breaker and #10 AWG sufficient for this?

wire size is based on nameplate HP NOT nameplate FLA....

Here's a current shot of the panel.

1779404955864.jpeg

Do you have 3Ø Delta? because skipping every 3rd breaker space indicates this And here's the junction box that's halfway down the run. This is where I was doing to potentially get power for my Bridgeport clone mill (single phase 230v or potentially 3 phase). This is where the braided 10 gauge wire is connected to the solid core 10 gauge wire with wire nuts.


That box is way too full

Any thoughts on how I should do this? If I have to run 8 gauge wire, I can live with that, but if 10 gauge is sufficient, I'm ok with sticking with that, of course.

I did a quick search and it appears that connecting solid to braided wires isn't unsafe.

#10 THWN is fine
 
To avoid these ads, REGISTER NOW!
Top Bottom