bulletpruf
Well-known member
Electrical stuff generally makes my head hurt, but I just got a new IR air compressor from Tractor Supply - https://www.tractorsupply.com/tsc/p...OPygWrEEKNKHvKCxlkIflG8CoJsP9jMxoCecoQAvD_BwE - it's single phase, two stage, 5 hp.
The specs state: 21.5 Full Load Amps, Recommended Breaker Amp Size 40, Recommended Wire Gauge <50 ft. 8 Gauge (8 AWG).
I have 230v connected to a 30 amp (i.e., smaller than recommended) breaker traveling about 30' to a box on the wall next to the compressor.
I do have the instructions, but they're generic for several different models of compressor.
I'm inclined to hard-wire the compressor, but I would be ok with a plug, too.
I guess my first step is to confirm that I have 8 gauge wire going from the panel to the box on the wall.
Scott

I don't have a recent picture of the panel since the compressor breaker was added, but I'll get one.


The specs state: 21.5 Full Load Amps, Recommended Breaker Amp Size 40, Recommended Wire Gauge <50 ft. 8 Gauge (8 AWG).
I have 230v connected to a 30 amp (i.e., smaller than recommended) breaker traveling about 30' to a box on the wall next to the compressor.
I do have the instructions, but they're generic for several different models of compressor.
I'm inclined to hard-wire the compressor, but I would be ok with a plug, too.
I guess my first step is to confirm that I have 8 gauge wire going from the panel to the box on the wall.
Scott

I don't have a recent picture of the panel since the compressor breaker was added, but I'll get one.