mike93lx
ALLIANCE MEMBER
High outlets don't work well with heavy cords
Here are my switches and garage door operators. Each wall fan is also on its own switch.Fair point. I'm doing the interior entirely myself, and it's looking like a buddy (electrician) and myself are going to do the electrical.
Looks like I have to play around with the switch layout as I'm right to the nose of max fill in 1, and just over in another. Back to the drawing board.



The first thing is to not recess your panel so you CAN run emt.I've pretty well settled on full metal interior and surface mounted EMT for my 30x40 stick build.
I'm planning to start small and just add circuits as required. I'm starting with
1. Outlets around the circumference, of the shop alternating on 2 circuits.
2. Outlets down the center of the ceiling switched for lights
3. Circuit with 2x Outdoor Floods and soffit lighting
4. 2x Outdoor outlets on a circuit.
I'm unsure if I want my garage door opener on a dedicated circuit since I plan to have a single outlet servicing 2x jackshaft openers. The 3rd door on the other side of the shop will probably just stay on a manual chain opener as it will seldom see use.
Regardless I'm trying to plan out some of these runs, and am looking for inspiration to keep it clean, simple, and have the ability to add all the circuits I need down the road without making it a cluttered mess. First debate is unsure if I want to run the EMT at outlet level, or like I've seen, run it near ceiling level and have drops going down to each outlet.
Basically just looking to see how all you surface mounters have done your shops, and looking for anything you wish you did differently, or tips for the process.
EDIT:
One question I'm unsure about is, how should I do the electrical for the few things I have outside (i.e. 2x floods, and 2x outlets)? Should I mount the boxes, etc, right away before I side/finish the interior, and stub EMT from the back of the boxes to the inside of the building? Then once the building is finished, continue the EMT run on the inside?
Panel will definitely be surface mounted. I could feed from the back, but then I would just need to stub in from the outside, versus inside through the slab. Unsure how I want to do it..The first thing is to not recess your panel so you CAN run emt.
Looks real good. I've been melting my brain trying to count/plan all the conductors I'll need leaving the panel, conduit/box fill, etc. Was also running into box fill issues when I had the switched stacked vertically, and I don't think I'd want box extensions on the switches.I put a tool / compressor room in my shed.
I put the panel in an interior wall in it.
I stubbed out emt through the roof of it and then went from there.
I stubbed out a spare piece of emt from the box so I can add circuit in the future if needed.


Looks like a good plan.Panel will definitely be surface mounted. I could feed from the back, but then I would just need to stub in from the outside, versus inside through the slab. Unsure how I want to do it..
Looks real good. I've been melting my brain trying to count/plan all the conductors I'll need leaving the panel, conduit/box fill, etc. Was also running into box fill issues when I had the switched stacked vertically, and I don't think I'd want box extensions on the switches.
I reworked the initial runs, little more EMT but it will result in less conductors jammed into 1 conduit, and less of a utter shitshow in that one box mounted near the ceiling, since I'll need to terminate 3 T90 runs into Romex before I stub it into the attic.
![]()
I'd probably lay it out if I had the structure up lol, and I'm sure I'll do something similar once the R-Panel is up to get things to lay in the flats nicely.Looks like a good plan.
I like the software you are using to lay it out - I used a roll of blue masking tape and put tape where I wanted boxes and switches….lol.
why? The marginal cost of double duplex is low, and the utility is high. I have never heard anyone say "I wished I'd installed single duplex outlets", but I hear the opposite a lot. Be consistent with circuit layout (circuit 1 on the left, 2 on the right. I try to get different colored hots in the boxes, and consistently use that as a guide.) and it's easy to make sure you plug the saw and vacuum into different circuits, even if they're not right next to each other. Make sure you have some low outlets, as high ones don't work well for heavy cords, nor for long ones -- they can create a tripping hazard when they're stretched out.All the outlets will be a single duplex in a 4x4 box.
That's a fair point, the outlets are quite cheap, maybe I should just do that, then I can have 1 of each circuit per box.why? The marginal cost of double duplex is low, and the utility is high. I have never heard anyone say "I wished I'd installed single duplex outlets", but I hear the opposite a lot. Be consistent with circuit layout (circuit 1 on the left, 2 on the right. I try to get different colored hots in the boxes, and consistently use that as a guide.) and it's easy to make sure you plug the saw and vacuum into different circuits, even if they're not right next to each other. Make sure you have some low outlets, as high ones don't work well for heavy cords, nor for long ones -- they can create a tripping hazard when they're stretched out.
What type of pipe strapping is that? I've seen content of people just using normal EMT straps mounted to the ridges, but I assume it's preferred to have it mounted to something like a stud/blocking.Here are my switches and garage door operators. Each wall fan is also on its own switch.
This was a fortunate accident.
On the south end of the shed, I ran the emt near the ceiling and dropped down to the boxes. In the rest of the building I ran emt along the purlins parallel to the floor.
My friend that was helping me mounted this box on the north wall about 9’ off the floor because he thought I was going to run the emt along that purlin and drop them down to boxes.
Now I had a box where I didn’t want it and unwanted holes in the interior metal.
I decided to put a motion light on a switch in that box. It has turned out to be a great feature. It helps light it up when you pull in at night. A lot more light than the openers put out and when you walk in, it turns on before you turn on the ceiling lights. If I want, I can also turn it off with the switch which is below it.
![]()
Not sure what the actual name is, I got it at Menards by the jar.What type of pipe strapping is that? I've seen content of people just using normal EMT straps mounted to the ridges, but I assume it's preferred to have it mounted to something like a stud/blocking.

Looks like I can get them on Amazon. It looks like you didn't have to bend any offsets of the box either?
I would cry
trade name is a minerallac strap, which is probably a brand name. They hold the pipe about 3/8” off the wall, which is usual box hole height. They use a carriage bolt to clamp, with a square hole to keep it from rotating , so they have a up and down orientation.What type of pipe strapping is that? I've seen content of people just using normal EMT straps mounted to the ridges, but I assume it's preferred to have it mounted to something like a stud/blocking.
www.crawfordelectricsupply.com
And even better are these; no bolt, screw, or nut and they fit both 1/2 and 3/4. For no more than what they are, the price is outrageous but that doesn't stop me from using them 90% of the time.
Caddy 812M clip for 1/2" or 3/4" EMT at Main Electric Supply
Conduit and pipe support for suspending from threaded rod, and direct attachment to beam clamp or structure.www.mainelectricsupply.com
Squeeze it together, pop it open with a screwdriver.How to you undo those?
Yep. Well that's my wording as I was playing off the thread title is all. Like I said, good old Mike got the boot none of us on the street ever ran into him again.That is a funny way to blame the women instead of the guy who destroyed his own family by being a complete jackass.
Deep boxesLooks slick. Hopefully mine turns out the same.
Did you use deep boxes or shallow?
this stuff is gold. thanks!I wire a lot of shops, with most of them being pole barns. I do my best to run everything high and drop as needed; it takes a little more time and material, but keeps wall spaces open for benches, cabinets, and junk in general. My first option is to run everything at the top of the wall, but there are times that plan goes to hell when the overhead door hardware says nope, ain't gonna happen. Then running on the ceiling, but close to the walls comes into play. I've done enough that I no longer draw a picture of what I'm doing but wouldn't be afraid to do it again. The main thing is to set everything up so there are no conduits being crossed because it looks like **** when that happens. I also put a gutter about six inches above the panel when using a load center; the knockouts in the panel don't line up and require everything to have an offset right from the start and once again, it looks like ****. A few six inch ******* from the panel to the gutter don't need anything and the the conduit can then be fanned out across the top of the gutter, keeping everything the same. You can also then run a circuit two directions through two different conduits and splice them in the gutter, leaving the wire nuts out of the panel. Another thing: nothing smaller than 3/4 leaves the panel or gutter; 1/2 is for drops, you can thank me later for that.
Do you often find that you use the same runs?I wire a lot of shops, with most of them being pole barns. I do my best to run everything high and drop as needed; it takes a little more time and material, but keeps wall spaces open for benches, cabinets, and junk in general. My first option is to run everything at the top of the wall, but there are times that plan goes to hell when the overhead door hardware says nope, ain't gonna happen. Then running on the ceiling, but close to the walls comes into play. I've done enough that I no longer draw a picture of what I'm doing but wouldn't be afraid to do it again. The main thing is to set everything up so there are no conduits being crossed because it looks like **** when that happens. I also put a gutter about six inches above the panel when using a load center; the knockouts in the panel don't line up and require everything to have an offset right from the start and once again, it looks like ****. A few six inch ******* from the panel to the gutter don't need anything and the the conduit can then be fanned out across the top of the gutter, keeping everything the same. You can also then run a circuit two directions through two different conduits and splice them in the gutter, leaving the wire nuts out of the panel. Another thing: nothing smaller than 3/4 leaves the panel or gutter; 1/2 is for drops, you can thank me later for that.
One of the big advantages of EMT is adding stuff. When I installed a minisplit in my garage, the electrical work took less than hour. Drilling the hole in the wall to get outside, and moving stuff so I could access a box buried behind a shelf were the hardest part. Leave room for future expansion, especially in runs leaving the panel. You'll probably need to run conduit when you add stuff, but usually you can add on to an existing run.Do you often find that you use the same runs?
I figured that for instance my outlets all fit in 1/2", and if I run another circuit I'll just run it in it's own EMT?
Makes sense! I always thought that with so many conductors derating would be an issue, but looking at the book I need over 24 conductors to go below 70% so it makes sense. Planning for 3/4 on the bigger and 1/2 on the drops like you said.I'll pull a few circuits through each conduit and drop as needed. One pipe might have eight number 12's, the next might have two 8's, two 10's, and two 12's. And 1/2" EMT is a PITA to keep straight when running horizontal, it's just too flimsy and isn't perfectly straight from the factory, requiring more straps; if you're running it off of a ladder more trips up and down are needed vs. 3/4.

A single gfci receptacle can protect all downstream. You don't have to go to a gfci breakerMakes sense! I always thought that with so many conductors derating would be an issue, but looking at the book I need over 24 conductors to go below 70% so it makes sense. Planning for 3/4 on the bigger and 1/2 on the drops like you said.
Also since I'm doing drops GFCI breakers seem to make more sense than pigtailing off outlets.. Oh how things add up..
Do you have an average % fill you try to stay below in your boxes? I'm doing the math and one of my outlet boxes seems to be pretty much stuffed to the **** (15mL spare), so I'm thinking I need to rework the layout around the switches.
![]()
I know, and I probably still could. It would just result in some ******* with the first outlet. Instead of pigtailing a drop at the JB at the ceiling and running down the drop to the outlet, I'd need to run down, pigtail off the hot end of the outlet, run up, and continue on.A single gfci receptacle can protect all downstream. You don't have to go to a gfci breaker
With conduit, that up and down is easy and only needs a little extra of two conductors per circuitI know, and I probably still could. It would just result in some ******* with the first outlet. Instead of pigtailing a drop at the JB at the ceiling and running down the drop to the outlet, I'd need to run down, pigtail off the hot end of the outlet, run up, and continue on.
Still an option, probably still cheaper too.
Two circuits per box is a reason to use a gfci breaker -- a two pole breaker will let you run them as MWBC, saving wire, conduit capacity, and current carrying conductor count.With conduit, that up and down is easy and only needs a little extra of two conductors per circuit
When you do your two circuits per box thing, make sure you aren't sharing neutrals as that will trip the gfci
Makes sense! I always thought that with so many conductors derating would be an issue, but looking at the book I need over 24 conductors to go below 70% so it makes sense. Planning for 3/4 on the bigger and 1/2 on the drops like you
Do you have an average % fill you try to stay below in your boxes? I'm doing the math and one of my outlet boxes
This is something I'm unfamiliar with tbh, but have been reading about today. I have a buddy who was an electrician, since retired, so lots of this will be confirmed with him.Two circuits per box is a reason to use a gfci breaker -- a two pole breaker will let you run them as MWBC, saving wire, conduit capacity, and current carrying conductor count.
Table 5C in CEC says that 7-24 insulated conductors has a correction factor of 0.70?Check your sources: 24 conductors would put you waaaaaay below 70%, even in CA.
Then you need to consider # conductors and size(s) for conduit fill and box fill.

Very generous compared to NEC.Table 5C in CEC says that 7-24 insulated conductors has a correction factor of 0.70?
I'm also no where near that at any point, it was just an example. With 3/4" main lines conduit fill isn't really on my radar right now. I'm sure down the road when I'm adding circuits and some 240 runs it will be, but I've been deep in the weeds of box fill.
EDIT: I just looked at the NEC, and the derating tables are vastly different. Here's the CEC for ref:
![]()
Nope. I just go with what seems right for what I'm doing. I try not to stuff the conduit, but it has happened before.Do you have an average % fill you try to stay below in your boxes?
You can do what you want, but if it were me, I'd run the lights the other direction with them butted up end to end, especially if the ceiling is ribbed metal (the ribs will run the long way and you can run the lights between them). At 40' deep (outside dimension), you're closer to 39 on the inside so four 8' fixtures would be about right. You can probably get by with two rows, but I'd have three if it were up to me; one down the middle and the outside rows about 3-4' off the sidewalls. You'd wind up with either two more or two less fixtures, but would eliminate a ton of conduit on the ceiling since you'd only have to pipe to the end fixture of each row then pull the wire through all of the lights. With the rows being 32' long, you could also add a 4' fixture to each row but that's probably overkill.
We call 'em minnies. The local supply house carries Minnerallac brand and if you ask for a box of ??" Minnerallac straps from the wrong salesman there's a good chance you find a box of one hole straps when the order comes out but everyone knows what a minnie is.I've always called those 'Mineralac straps' but they're also known as conduit hangers.