To avoid these ads, REGISTER NOW!

HVAC Zone Damper help/advice

sgrammel

Well-known member
Joined
Oct 27, 2009
Messages
1,342
Location
The 'couv
I have an HVAC system with two zones (upstairs and downstairs). It has the Honeywell power actuator to open/close the damper. The issue I face is that when the upstairs zone is operating and downstairs is 'off', I still get some airflow in the downstairs registers. This can end up making downstairs too cold.

I think I am correct in saying that the damper won't seal 100% some some airflow to the downstairs zone is expected....It just seems too much for me.

So the question I have is how to adjust the damper? It is rectangular if that matters. If I disconnect the motor from the damper rod and rotate it manually, will it be fully open at one end of the rotation, and fully closed at the other? If so, if I rotate it to the fully open or closed position and then re-attach the motor, will that help with the issue?IMG_2897.JPG
 
Last edited:
To avoid these ads, REGISTER NOW!

DGersic

Well-known member
Joined
Mar 12, 2017
Messages
6,237
Location
DeKalb, IL
I have what looks like the same damper here.

IMG_9264.jpegIMG_9265.jpegIMG_9266.jpegIMG_9267.jpeg

Your picture doesn’t show how far the damper is closing. Poke your phone around the corner and have a look at that first.

If I’m reading it correctly, the damper can be adjusted to stop at several positions, so maybe yours just needs to be adjusted.
 

Ohmthis

Well-known member
Joined
Jan 20, 2013
Messages
2,992
Location
Outside of Louisville KY
Exactly as stated above. Those adjustable, get a picture of where it is at the closed position. One question I have, is there a bypass damper. This will go between the supply (before dampers) and the return. If there isn’t one, that supply damper is adjusted to let the overflow of pressure bleed off into the downstairs zone.
 

Codyboy

Well-known member
Joined
Jan 31, 2019
Messages
1,577
Location
S.E. TEXAS
I have the same zone control and damper motors.
On mine the issue is the damper flap /door whatever and the seal inside the housing. The seal is no longer there , so the flap has nothing to completely close off the air flow.

Kind of like a car door that has no weatherstripping .
 
To avoid these ads, REGISTER NOW!

PoorUB

Well-known member
Joined
Mar 29, 2021
Messages
11,582
Location
Fargo, ND
I never set the zone dampers to close completely anyway, so I wouldn't worry about it unless it causes some other issue.
The only repair is to replace the damper. No one has replacement parts for these, other than the actuator/motor.
 

fitter30

Well-known member
Joined
Jun 23, 2019
Messages
2,951
Location
Peace Valley,mo
Good damper are opposed blade with rubber tipped blades and seals for the sides of the blades to cut down on leakage. Damper adjust with actuator in closed position don't worry about 100% open. Blade at 90% open or more is flowing 100%

12609.png
 
Last edited:

JohnX14

Well-known member
Joined
Jun 2, 2014
Messages
549
Location
Boston 'burbs
A lot of systems have some feed to the 2nd zone when the 1st calls, and vice versa. Most installers design them that way. You either blow some air into the non-calling zone, or you install a bypass damper into the ductwok and it dumps back into the return. Better off dumping a small % into the zone that isn't calling. The return is pulling from the whole house either way
 
To avoid these ads, REGISTER NOW!
Top Bottom